Inverter cable size: chart for 1000 W, 2000 W and 3000 W inverters at 12, 24 and 48 V

On a 12 V battery with a short run (1.5 m, about 5 ft, from battery to inverter), a 1000 W inverter needs 25 mm² (4 AWG) cable with a 125 A fuse, a 2000 W inverter needs 70 mm² (1/0 AWG) with a 250 A fuse, and a 3000 W inverter needs 95 mm² (3/0 AWG) with a 350 A fuse. At 24 V the same 3000 W inverter needs 35 mm² (3 AWG), at 48 V just 16 mm² (6 AWG). For your own length and voltage, use the cable size calculator.

Below: how to get the current from the inverter’s watts, the full chart for 500 to 5000 W at 12, 24 and 48 V, how the size grows with the cable length, the fuse between battery and inverter, why big inverters run at 24 or 48 V, and the mistakes that make an inverter shut down under load.

From inverter watts to battery current

The cable carries DC current from the battery, not the AC power the inverter delivers. The inverter also loses some energy as heat, so the battery has to supply more than the load uses:

  1. 1

    Current (A) = continuous watts ÷ (battery voltage × inverter efficiency). Most inverters convert 85–90% of the battery power into AC at full load. This guide uses 90%.

  2. 2

    Example at 12 V: 2000 W ÷ (12 V × 0.90) = 185 A. Without the losses it would be 167 A, which is why sizing on watts ÷ volts alone undersizes the cable.

  3. 3

    Low battery: the current rises as the voltage falls. The same 2000 W at 11.5 V takes 193 A; at 12 V with 85% efficiency it takes 196 A. Both stay below the 250 A fuse the chart gives for 185 A, because the fuse sits 25% above the continuous current.

  4. 4

    Surge vs continuous: size the cable on the continuous rating. The surge figure on the datasheet lasts a few seconds when a motor or a compressor starts; the fuse, sized above the continuous current, has to let it through, and the cable has to carry the fuse current.

If your inverter will never run near its rating, you can size on the largest load you actually run: a 3000 W inverter that only ever powers a 1200 W kettle draws about 111 A at 12 V. Size on the inverter’s rating anyway if someone could plug in more later.

Inverter cable size chart (1.5 m one way)

Assumptions: stranded copper (0.0175 Ω·mm²/m at 20 °C), 1.5 m (5 ft) from battery to inverter, counted twice for the positive and the negative (3 m of cable in total), at most 2% voltage drop, 90% inverter efficiency. The fuse is the next standard size at or above 1.25 × the current, and the cable must carry the fuse current (ABYC E-11 ratings, 105 °C insulation, one cable in free air). Each size is what the cable size calculator gives for that current: enter the amps from the table, your length and 2%.

12 V inverterBattery currentCableFuse
500 W46 A16 mm² · 6 AWG60 A
1000 W93 A25 mm² · 4 AWG125 A
1500 W139 A35 mm² · 2 AWG175 A
2000 W185 A70 mm² · 1/0 AWG250 A
3000 W278 A95 mm² · 3/0 AWG350 A
24 V inverterBattery currentCableFuse
500 W23 A4 mm² · 12 AWG30 A
1000 W46 A6 mm² · 10 AWG60 A
1500 W69 A16 mm² · 6 AWG100 A
2000 W93 A25 mm² · 4 AWG125 A
3000 W139 A35 mm² · 3 AWG175 A
5000 W231 A70 mm² · 2/0 AWG300 A
48 V inverterBattery currentCableFuse
500 W12 A1 mm² · 18 AWG15 A
1000 W23 A2.5 mm² · 14 AWG30 A
1500 W35 A6 mm² · 10 AWG50 A
2000 W46 A6 mm² · 10 AWG60 A
3000 W69 A16 mm² · 6 AWG100 A
5000 W116 A25 mm² · 4 AWG150 A

On these short runs heat sets most of the sizes, not the voltage drop: 2000 W at 12 V would need only about 41 mm² for 2% drop, but the 250 A fuse calls for a cable rated for 250 A. The metric size and the AWG gauge are each the next size up with at least the area needed, so they don’t always match exactly: 6 AWG is 13.3 mm², and the next metric size up is 16 mm².

Your inverter’s manual comes first. Many manuals give a cable size and a fuse for each cable length, and the terminals accept a limited range of lugs. The chart is a starting point; where it and the manual disagree, use the larger cable.

How the cable size grows with length

Same method, same 2% drop and 90% efficiency, longer runs. The length is one way; the return on the negative is already counted.

One way1000 W at 12 V (93 A)2000 W at 12 V (185 A)3000 W at 24 V (139 A)5000 W at 48 V (116 A)
1 m (3 ft)25 mm² · 4 AWG70 mm² · 1/0 AWG35 mm² · 3 AWG25 mm² · 4 AWG
1.5 m (5 ft)25 mm² · 4 AWG70 mm² · 1/0 AWG35 mm² · 3 AWG25 mm² · 4 AWG
2 m (7 ft)35 mm² · 2 AWG70 mm² · 2/0 AWG35 mm² · 3 AWG25 mm² · 4 AWG
3 m (10 ft)50 mm² · 1 AWG95 mm² · 3/0 AWG35 mm² · 2 AWG25 mm² · 4 AWG
5 m (16 ft)70 mm² · 3/0 AWG150 mm² · 300 kcmil70 mm² · 1/0 AWG25 mm² · 4 AWG

Up to about 1.5 m the fuse decides and the size doesn’t change; beyond that the voltage drop takes over and the copper grows in proportion to the length. A 2000 W inverter at 12 V needs more than twice the copper at 5 m than at 1.5 m. The cheapest fix is almost always a shorter run: mount the inverter next to the battery and run the AC side, which carries a fraction of the current, to where you need it.

Fuse or breaker between battery and inverter

  • Rating: at least 1.25 × the continuous battery current, so it doesn’t blow at full load, and never above the current the cable is rated to carry. The fuse protects the cable, not the inverter.
  • Position: on the positive cable, as close to the battery as you can. Any length of cable before the fuse is unprotected. ABYC E-11, the standard for boats, asks for the fuse within 7 inches (18 cm) of the battery in most cases (ABYC E-11 excerpts).
  • Type: a fuse or DC breaker rated for the system’s DC voltage and for the short-circuit current your battery can deliver. A lithium battery can deliver a very high current into a short; its datasheet usually states which fuse or breaker it asks for.
  • One per inverter: if a busbar feeds several loads, each cable leaving it needs its own fuse, sized for that cable.

Why big inverters run at 24 V or 48 V

For the same power, doubling the voltage halves the current. A 3000 W inverter draws 278 A at 12 V, 139 A at 24 V and 69 A at 48 V, and the cable goes from 95 mm² to 35 mm² to 16 mm² over the same 1.5 m. In the same cable the losses fall even faster, with the square of the current, and the 2% drop allowed at 48 V is four times as many volts as at 12 V.

That’s why the chart lists 5000 W only at 24 and 48 V: at 12 V a 5000 W inverter would draw over 460 A, and its fuse would go beyond 500 A, outside the range of a single cable in the calculator. For a 48 V bank, see the 48 V LiFePO4 voltage chart; for how long the battery runs the inverter, the battery runtime calculator.

Common mistakes

  • Counting only one way. The current goes out on the positive and back on the negative. 1.5 m from battery to inverter is 3 m of cable for the voltage drop.
  • Undersized cable. 2000 W at 12 V through 16 mm² over 1.5 m loses 0.61 V (5%) and turns about 110 W into heat in the cable, and 16 mm² is not rated for 185 A. The inverter sees the battery voltage minus that drop, so a battery that still has plenty of charge triggers the low-voltage alarm or shutdown as soon as a big load starts. The right 70 mm² cable loses 0.14 V.
  • Poor crimps. A lug crimped with pliers or a hammer tool adds resistance at one point, which heats up under load. Use lugs made for the cable size and a crimper made for those lugs, and check the terminal torque from the manual.
  • A thinner negative. The negative carries the same current as the positive. Both cables must be the same size, and so must the cable through a shunt or a main switch.
  • Sizing on the surge. It leads to a fuse far above the continuous current and then to a cable that isn’t protected. Size on the continuous rating and let the fuse handle the surge.

The voltage drop of the cable adds to the battery’s own voltage sag under load. On a LiFePO4 battery the resting voltage barely moves between 30% and 80% (see the LiFePO4 voltage chart), so a voltage that collapses only under heavy load usually points at the cable, the connections or the fuse holder.

See the current live

With a Victron SmartShunt on the battery, the Deeck app on iPhone shows the battery current and voltage live: switch on a big load and you see what the inverter really draws and how far the voltage sags. Deeck also reads Victron inverters: output power (W, or VA on Phoenix), state and alarms, and where the device sends them, AC input, state of charge and temperature.

Over Bluetooth it reads Phoenix inverters with Bluetooth, the Inverter RS, the Multi RS and a MultiPlus with the VE.Bus Smart dongle; inverters without Bluetooth appear through a GX device. Victron devices nearby over Bluetooth are free in Deeck. More: Phoenix inverter on iPhone and MultiPlus on iPhone.

Questions people ask

What size cable for a 2000W inverter on 12V?

About 185 A at 12 V with 90% inverter efficiency. Over 1.5 m one way at 2% drop that’s 70 mm² (1/0 AWG) with a 250 A fuse. At 3 m one way it grows to 95 mm² (3/0 AWG), at 5 m to 150 mm² (300 kcmil). The inverter’s manual has the final word.

What size cable for a 3000W inverter?

Over 1.5 m one way at 2% drop: 95 mm² (3/0 AWG) at 12 V for about 278 A, 35 mm² (3 AWG) at 24 V for 139 A, and 16 mm² (6 AWG) at 48 V for 69 A.

What size fuse for a 3000W inverter?

The next standard fuse at or above 1.25 × the continuous battery current: 350 A at 12 V (278 A), 175 A at 24 V (139 A), 100 A at 48 V (69 A). The cable must be rated for the fuse current, and the fuse goes on the positive, as close to the battery as possible.

What size cable for a 1000W inverter?

At 12 V the inverter draws about 93 A: 25 mm² (4 AWG) with a 125 A fuse up to 1.5 m one way, 35 mm² (2 AWG) at 2 m, 50 mm² (1 AWG) at 3 m. At 24 V it’s 46 A and 6 mm² (10 AWG) with a 60 A fuse over 1.5 m.

Does a 24V inverter need thinner cable?

Yes. For the same power the current halves, and the 2% drop allows twice as many volts, so the voltage-drop size falls to a quarter. A 2000 W inverter needs 70 mm² at 12 V and 25 mm² at 24 V over 1.5 m; at short lengths the fuse rating, not the voltage drop, sets the size.

Does the cable length include the negative?

Yes. Measure the one-way distance from the battery to the inverter and double it for the voltage drop, because the current flows out on the positive and back on the negative. The cable size calculator does the doubling for you.

On the dash and on your wrist

Sized right. Now see what it draws.

Seeing it is free. Having it on the dash and on your wrist is Deeck Plus.

Put it on CarPlay and Watch Download the app free

Free app · Deeck Plus €39.99 a year · cancel anytime · 14 days to change your mind