12 V cable size calculator: wire gauge in mm² and AWG, with voltage drop

This 12 V cable size calculator gives you the minimum wire size for a DC circuit in an RV, camper van, boat or off-grid cabin: enter the current in amps (or the power in watts), the cable length and the voltage drop you accept, and you get the cable size in mm² and in AWG, the real voltage drop and an indicative fuse. It works for 12, 24 and 48 V systems.

It sizes the cable for the voltage drop over the full loop, out on the positive and back on the negative, then checks that the cable can carry the fuse current without overheating, and gives you the larger of the two. Everything runs in your browser, nothing is sent anywhere, and the link keeps your numbers so you can share them.

Calculate your cable size

Load
Fill in one of the two: the other follows (amps = watts ÷ volts). For an inverter, add about 10% to the watts for its losses.
Cable
From the battery (or the fuse box) to the device. The calculator doubles it for the return on the negative cable.
3% suits most loads. Choose 1–2% for chargers, inverters and the main battery cables.

Stranded copper conductor, resistivity ρ = 0.0175 Ω·mm²/m (at 20 °C).

Result

Minimum cable size–

Section for the voltage drop
–
Heat check, carries the fuse
–
Voltage drop with 6 mm²
–
Voltage drop with 8 AWG
–
Voltage at the device
–
Power lost in the cable
–

Indicative fuse: –

The next standard fuse at or above 1.25 × the current, so it doesn’t blow at full load. The fuse protects the cable: the cable must be rated for at least the fuse current. Where your device’s manual names a fuse or a cable size, use those.

Heat check: ABYC E-11 ratings for copper with 105 °C insulation, one cable in free air, outside the engine bay. PVC cable, bundles, conduit and engine bays carry less: check your cable’s datasheet.

section (mm²) = 2 × L (m) × I (A) × 0.0175 ÷ (V × drop %) · drop (V) = 2 × L × I × 0.0175 ÷ section · fuse ≥ 1.25 × I

A calculator is a starting point, not a wiring plan. The installation manual of your charger, inverter or battery and the current rating on your cable’s datasheet come first; when in doubt, choose the next size up: a thicker cable costs a little more and runs cooler.

How the calculator works

A cable is a small resistor. The current that flows through it loses some voltage on the way, and that loss grows with the length and the current and shrinks with the cross-section. On a 12 V system a few tenths of a volt matter: a fridge, a pump or a DC-DC charger sees less voltage than the battery holds.

  1. 1

    Total length: the current goes out on the positive and comes back on the negative, so the loop is twice the one-way length. 3 m from the battery to a fridge means 6 m of cable.

  2. 2

    Allowed drop in volts: system voltage × drop %. At 12 V and 3%, that’s 0.36 V.

  3. 3

    Section for the drop: mm² = 2 × length (m) × current (A) × 0.0175 ÷ allowed drop (V). For 20 A over 3 m: 2 × 3 × 20 × 0.0175 ÷ 0.36 = 5.83 mm².

  4. 4

    Commercial size: the calculator rounds up to the next metric size (here 6 mm²) and, separately, to the next AWG gauge with at least that area (here 8 AWG, 8.37 mm²).

  5. 5

    Heat check: the indicative fuse is the next standard size at or above 1.25 × the current (25 A here). The cable has to carry that current; if the voltage-drop size can’t, the calculator moves up to a size that can.

0.0175 Ω·mm²/m is the resistivity of copper at 20 °C. A warm cable has a higher resistance, roughly 20% more at 70 °C, which is one more reason to round up rather than down. The ABYC E-11 standard for boats asks for the same two checks, voltage drop and current rating, and says to use the larger conductor when they disagree (ABYC E-11 excerpts). Victron’s free book on DC wiring explains the same physics with examples (Wiring Unlimited, DC wiring).

12 V cable size chart (3% voltage drop)

The table shows the result of the calculator at 12 V and 3% drop, with the heat check included. The length is one way: the return on the negative is already counted. Each cell gives the metric size and the AWG gauge with at least the same area.

Current1 m (3 ft)2 m (7 ft)3 m (10 ft)5 m (16 ft)8 m (26 ft)
5 A1 mm² · 18 AWG1 mm² · 16 AWG1.5 mm² · 14 AWG2.5 mm² · 12 AWG4 mm² · 10 AWG
10 A1 mm² · 16 AWG2.5 mm² · 14 AWG4 mm² · 12 AWG6 mm² · 10 AWG10 mm² · 8 AWG
15 A1.5 mm² · 14 AWG4 mm² · 12 AWG6 mm² · 10 AWG10 mm² · 8 AWG16 mm² · 6 AWG
20 A2.5 mm² · 14 AWG4 mm² · 10 AWG6 mm² · 8 AWG10 mm² · 6 AWG16 mm² · 4 AWG
30 A4 mm² · 12 AWG6 mm² · 8 AWG10 mm² · 6 AWG16 mm² · 4 AWG25 mm² · 3 AWG
50 A10 mm² · 8 AWG10 mm² · 6 AWG16 mm² · 4 AWG25 mm² · 3 AWG50 mm² · 1 AWG
80 A16 mm² · 6 AWG16 mm² · 4 AWG25 mm² · 3 AWG50 mm² · 1 AWG70 mm² · 2/0 AWG
100 A25 mm² · 4 AWG25 mm² · 4 AWG35 mm² · 2 AWG50 mm² · 1/0 AWG95 mm² · 3/0 AWG
150 A35 mm² · 2 AWG35 mm² · 2 AWG50 mm² · 1/0 AWG95 mm² · 3/0 AWG120 mm² · 250 kcmil
200 A70 mm² · 1/0 AWG70 mm² · 1/0 AWG70 mm² · 2/0 AWG120 mm² · 4/0 AWG185 mm² · 350 kcmil

In the short columns at high current, heat sets the size rather than the voltage drop: 100 A over 1 m would need only about 10 mm² for 3% drop, but a 125 A fuse calls for a cable that carries 125 A. On the long runs it’s the other way round, and the voltage drop asks for far more copper than heat would.

At 24 V the allowed drop in volts doubles, so for the same current the voltage-drop section halves; at 48 V it’s a quarter. For the same power it’s even better, because the current halves too: a 1,200 W load needs a quarter of the copper at 24 V that it needs at 12 V, as far as voltage drop goes.

Which voltage drop to choose

  • 1–2%: charging and the main cables. Battery to inverter, DC-DC charger, solar charger to battery, battery to the main busbar. Every tenth of a volt lost here slows charging or makes an inverter trip early. Victron’s Wiring Unlimited suggests aiming below 2.5%.
  • 3%: most loads. Fridge, water pump, heater, electronics, navigation lights. ABYC E-11 uses 3% for circuits where the voltage drop must stay small.
  • Up to 5%: loads that don’t mind. Cabin lights and simple resistive loads. ABYC allows up to 10% for non-critical lighting; a lower figure keeps LED drivers and USB chargers happy.

Voltage drop is not only a performance question. A DC-DC charger like the Victron Orion XS decides from its input voltage whether the engine is running, so a long, thin input cable can stop charging too early; see Orion XS LiFePO4 settings. A thin cable between the solar charger and the battery means the battery gets less than the absorption voltage you set, because part of it is lost on the way; see MPPT LiFePO4 settings.

mm² and AWG: reading both

Europe sizes cable by its copper cross-section in mm²; North America uses AWG, where a smaller number means a thicker cable and sizes above 4/0 continue in kcmil. The two scales don’t line up: 6 mm² sits between 10 AWG (5.26 mm²) and 8 AWG (8.37 mm²). That’s why the calculator chooses each one on its own, always the next size up with at least the area you need, and shows the voltage drop for both.

AWGAreaNearest metric size at or above
14 AWG2.08 mm²2.5 mm²
12 AWG3.31 mm²4 mm²
10 AWG5.26 mm²6 mm²
8 AWG8.37 mm²10 mm²
6 AWG13.3 mm²16 mm²
4 AWG21.2 mm²25 mm²
2 AWG33.6 mm²35 mm²
1/0 AWG53.5 mm²70 mm²
2/0 AWG67.4 mm²70 mm²
4/0 AWG107 mm²120 mm²

Once the cables are in: see the system live

Good cables show up in the numbers: the charge power you expected, a battery that reaches full, a fridge that never complains. Deeck puts those numbers on one deck on your iPhone: the battery voltage, current and state of charge from a Victron SmartShunt, next to the power of your solar charger, DC-DC charger and shore charger.

  • Free on iPhone, with your Victron devices: the live deck over Bluetooth when you’re near your system, 7 days of history, widgets and Siri.
  • Deeck Plus, €39.99 a year: CarPlay and Apple Watch, remote access through Deeck Bridge or VRM, and the Bluetooth BMS of your lithium battery next to your Victron.

Planning the battery too? The battery runtime calculator tells you how long it lasts with your loads, and the LiFePO4 voltage chart what its voltage really says.

Questions people ask

What size cable do I need for 12V 100A?

It depends on the length. At 3% voltage drop, with the return counted: 25 mm² (4 AWG) up to 2 m one way, 35 mm² (2 AWG) at 3 m, 50 mm² (1/0 AWG) at 5 m and 95 mm² (3/0 AWG) at 8 m. On the short runs the size comes from the 125 A fuse the cable has to carry, not from the voltage drop.

What gauge wire for a 2000W inverter on 12V?

2,000 W at 12 V is about 167 A, closer to 185 A once you add the inverter’s losses. Over 1.5 m one way at 2% drop the calculator gives 70 mm² or 1/0 AWG, with a 250 A fuse. The inverter’s manual has the final word: it usually gives a cable size and a fuse for each cable length. Every common inverter size at 12, 24 and 48 V is in the inverter cable size chart.

How do I calculate voltage drop in a 12V cable?

Voltage drop (V) = 2 × one-way length (m) × current (A) × 0.0175 ÷ cross-section (mm²). For 20 A over 3 m of 6 mm²: 2 × 3 × 20 × 0.0175 ÷ 6 = 0.35 V, which is 2.9% of 12 V.

Does the cable length include the negative wire?

Yes. The current flows out on the positive and back on the negative, and both lose voltage. Enter the one-way distance from the battery to the device; the calculator doubles it. If the negative goes to a busbar or a shunt by a different route, use the longer of the two distances.

What size fuse do I need for my cable?

Pick a fuse a little above the load current, about 1.25 times, so it doesn’t blow at full load, and never above what the cable is rated to carry: the fuse is there to protect the cable. Fit it as close to the battery as you can. If the device’s manual specifies a fuse, use that one.

Is it a problem to use a thicker cable than needed?

No. A thicker cable loses less voltage and runs cooler; it only costs more and is harder to bend. Check that it fits the device’s terminals and that the lugs match the cable size.