12V cable size chart: wire size in mm² and AWG by current and cable length
At 12 V and at most 3% voltage drop, 20 A over 3 m (10 ft) from the battery needs 6 mm² (8 AWG) cable with a 25 A fuse, 30 A over 3 m needs 10 mm² (6 AWG) with a 40 A fuse, and 100 A over 3 m needs 35 mm² (2 AWG) with a 125 A fuse. The length in the chart is one way; the return on the negative is already counted. For a current or a length that isn’t in the chart, use the cable size calculator.
Below: the 12 V and 24 V charts from 5 to 200 A and 1 to 10 m, why the length counts twice, when a 10% drop is fine, the fuse that protects the cable, a worked example, and when to choose a larger size. Every size in the charts is what the calculator gives for that current and length.
How to read the chart
Find the row with your load’s current and the column with the distance from the battery (or the fuse box) to the device. The cell gives the smallest cable that keeps the voltage drop within 3% and can carry the fuse current without overheating. The assumptions:
- Stranded copper, 0.0175 Ω·mm²/m at 20 °C.
- Length one way: 1 m (3 ft), 3 m (10 ft), 5 m (16 ft) and 10 m (33 ft). The calculation doubles it for the negative.
- Current: the continuous current of the load or charger, in amps. If you only know the watts: amps = watts ÷ volts.
- Fuse: the next standard size at or above 1.25 × the current, shown in brackets next to the current.
- Heat check: the cable must carry the fuse current, using the ABYC E-11 ratings for copper with 105 °C insulation, one cable in free air, outside the engine bay.
- Two scales: the metric size and the AWG gauge are each the next size up with at least the area needed, so they don’t always line up: 6 mm² sits between 10 AWG and 8 AWG.
12V cable size chart (3% voltage drop)
| Current (fuse) | 1 m (3 ft) | 3 m (10 ft) | 5 m (16 ft) | 10 m (33 ft) |
|---|---|---|---|---|
| 5 A (7.5 A fuse) | 1 mm² · 18 AWG | 1.5 mm² · 14 AWG | 2.5 mm² · 12 AWG | 6 mm² · 10 AWG |
| 10 A (15 A fuse) | 1 mm² · 16 AWG | 4 mm² · 12 AWG | 6 mm² · 10 AWG | 10 mm² · 6 AWG |
| 15 A (20 A fuse) | 1.5 mm² · 14 AWG | 6 mm² · 10 AWG | 10 mm² · 8 AWG | 16 mm² · 4 AWG |
| 20 A (25 A fuse) | 2.5 mm² · 14 AWG | 6 mm² · 8 AWG | 10 mm² · 6 AWG | 25 mm² · 4 AWG |
| 30 A (40 A fuse) | 4 mm² · 12 AWG | 10 mm² · 6 AWG | 16 mm² · 4 AWG | 35 mm² · 2 AWG |
| 40 A (50 A fuse) | 6 mm² · 10 AWG | 16 mm² · 6 AWG | 25 mm² · 4 AWG | 50 mm² · 1 AWG |
| 50 A (70 A fuse) | 10 mm² · 8 AWG | 16 mm² · 4 AWG | 25 mm² · 3 AWG | 50 mm² · 1/0 AWG |
| 60 A (80 A fuse) | 10 mm² · 8 AWG | 25 mm² · 4 AWG | 35 mm² · 2 AWG | 70 mm² · 2/0 AWG |
| 80 A (100 A fuse) | 16 mm² · 6 AWG | 25 mm² · 3 AWG | 50 mm² · 1 AWG | 95 mm² · 3/0 AWG |
| 100 A (125 A fuse) | 25 mm² · 4 AWG | 35 mm² · 2 AWG | 50 mm² · 1/0 AWG | 120 mm² · 4/0 AWG |
| 150 A (200 A fuse) | 35 mm² · 2 AWG | 50 mm² · 1/0 AWG | 95 mm² · 3/0 AWG | 150 mm² · 300 kcmil |
| 200 A (250 A fuse) | 70 mm² · 1/0 AWG | 70 mm² · 2/0 AWG | 120 mm² · 4/0 AWG | 240 mm² · 400 kcmil |
On short runs heat sets the size, not the voltage drop: 200 A needs 70 mm² at 1 m and at 3 m alike, because the cable has to carry its 250 A fuse. On long runs the voltage drop takes over and the copper grows with the length: at 20 A it goes from 2.5 mm² at 1 m to 25 mm² at 10 m. The cheapest way to a thinner cable is almost always a shorter run: mount the charger or the inverter close to the battery.
24V cable size chart (3% voltage drop)
At 24 V the same 3% allows twice as many volts. For the same current the section needed for the voltage drop halves; for the same power, where the current halves too, it falls to a quarter. 20 A over 3 m needs 4 mm² (12 AWG) at 24 V instead of 6 mm² (8 AWG) at 12 V. The fuse doesn’t depend on the voltage, so on short runs the heat check decides more often: 100 A needs 25 mm² at 1, 3 and 5 m.
| Current (fuse) | 1 m (3 ft) | 3 m (10 ft) | 5 m (16 ft) | 10 m (33 ft) |
|---|---|---|---|---|
| 5 A (7.5 A fuse) | 1 mm² · 18 AWG | 1 mm² · 18 AWG | 1.5 mm² · 16 AWG | 2.5 mm² · 12 AWG |
| 10 A (15 A fuse) | 1 mm² · 18 AWG | 1.5 mm² · 14 AWG | 2.5 mm² · 12 AWG | 6 mm² · 10 AWG |
| 15 A (20 A fuse) | 1 mm² · 18 AWG | 2.5 mm² · 12 AWG | 4 mm² · 10 AWG | 10 mm² · 8 AWG |
| 20 A (25 A fuse) | 1.5 mm² · 16 AWG | 4 mm² · 12 AWG | 6 mm² · 10 AWG | 10 mm² · 6 AWG |
| 30 A (40 A fuse) | 4 mm² · 12 AWG | 6 mm² · 10 AWG | 10 mm² · 8 AWG | 16 mm² · 4 AWG |
| 40 A (50 A fuse) | 6 mm² · 10 AWG | 6 mm² · 8 AWG | 10 mm² · 6 AWG | 25 mm² · 4 AWG |
| 50 A (70 A fuse) | 10 mm² · 8 AWG | 10 mm² · 8 AWG | 16 mm² · 6 AWG | 25 mm² · 3 AWG |
| 60 A (80 A fuse) | 10 mm² · 8 AWG | 10 mm² · 6 AWG | 16 mm² · 4 AWG | 35 mm² · 2 AWG |
| 80 A (100 A fuse) | 16 mm² · 6 AWG | 16 mm² · 6 AWG | 25 mm² · 4 AWG | 50 mm² · 1 AWG |
| 100 A (125 A fuse) | 25 mm² · 4 AWG | 25 mm² · 4 AWG | 25 mm² · 3 AWG | 50 mm² · 1/0 AWG |
| 150 A (200 A fuse) | 35 mm² · 2 AWG | 35 mm² · 2 AWG | 50 mm² · 1 AWG | 95 mm² · 3/0 AWG |
| 200 A (250 A fuse) | 70 mm² · 1/0 AWG | 70 mm² · 1/0 AWG | 70 mm² · 1/0 AWG | 120 mm² · 4/0 AWG |
Why the cable length counts twice
The current goes out to the device on the positive cable and comes back to the battery on the negative, and both cables lose voltage. A device 3 m from the battery has 6 m of cable in its circuit. The chart and the calculator take the one-way distance and double it. If the negative takes a different route, through a busbar or a shunt, use the longer of the two distances, and give the negative the same size as the positive: it carries the same current.
3% or 10%: how much voltage drop to accept
3% of 12 V is 0.36 V. That’s the usual limit for anything that cares about voltage: fridges, pumps, electronics, and the cables of solar and DC-DC chargers, where every tenth of a volt lost is charge that never reaches the battery. For the main battery cables, chargers and inverters, 1–2% is better.
Lights and other loads that don’t mind a little less voltage can take up to 10%. On long runs that allows much thinner cable (12 V, 10% drop, same fuse and heat check):
- 5 A of LED lights over 10 m: 1.5 mm² (14 AWG) instead of 6 mm² (10 AWG) at 3%.
- 10 A over 5 m: 1.5 mm² (14 AWG) instead of 6 mm² (10 AWG).
- 20 A over 5 m: 4 mm² (12 AWG) instead of 10 mm² (6 AWG).
On short runs 10% changes nothing: the cable still has to carry the fuse. The calculator offers 1 to 5%; for a 10% run, use these examples or the formula in the worked example below.
Worked example: 20 A over 3 m at 12 V
- 1
Total length: 3 m one way × 2 = 6 m of cable.
- 2
Allowed drop: 12 V × 3 ÷ 100 = 0.36 V.
- 3
Section for the drop: 0.0175 × 6 m × 20 A ÷ 0.36 V = 5.8 mm².
- 4
Fuse: 1.25 × 20 A = 25 A, which is a standard size: a 25 A fuse.
- 5
Heat check: a cable rated for 25 A is far thinner than 5.8 mm², so here the voltage drop decides.
- 6
Commercial size: the next size up from 5.8 mm² is 6 mm², or 8 AWG. With 6 mm² the real drop is 0.35 V, 2.9%.
The fuse: close to the battery, rated for the cable
- The fuse protects the cable. In a short circuit it has to blow before the cable overheats, so the cable must be rated for at least the fuse current. That’s why the chart shows the fuse next to each current and checks every size against it.
- Close to the battery: on the positive, as near the battery terminal as you can. Any cable before the fuse is unprotected.
- Not too small either: about 1.25 × the continuous current, so it doesn’t blow at full load.
- The manual first: where the manual of your charger, inverter or device names a fuse or a cable size, use those.
- One per branch: every cable leaving a busbar or a fuse box needs its own fuse, sized for that cable.
Bundles, conduit and the engine bay: go a size up
The heat check assumes one cable in free air, outside the engine bay. Cables bundled together, in conduit or in a hot engine bay shed heat less well and are rated for less current; PVC insulation also carries less than 105 °C insulation. In those places choose a larger size than the chart gives and check the rating on your cable’s datasheet. A thicker cable never hurts electrically: it loses less voltage and runs cooler. Just check that it fits the terminals and the lugs.
Inverter cables
An inverter draws more current than its watts ÷ volts because of its own losses, and its surge matters when you choose the fuse. The inverter cable size chart gives cable and fuse for the common inverter sizes at 12, 24 and 48 V.
Know the real current with Deeck
A chart is only as good as the current you put in. With a Victron SmartShunt, a BMV or another battery monitor that Deeck reads, the app shows the battery current and voltage live on your iPhone: switch the load on, see how many amps it really draws, and use that number in the chart or the calculator. Victron devices nearby over Bluetooth are free in Deeck.
Questions people ask
What size wire for 12V 30 amp?
At 3% voltage drop, with a 40 A fuse: 4 mm² (12 AWG) for 1 m one way, 10 mm² (6 AWG) for 3 m, 16 mm² (4 AWG) for 5 m and 35 mm² (2 AWG) for 10 m.
What gauge wire for 12V 20 amps?
At 3% drop, with a 25 A fuse: 2.5 mm² (14 AWG) for 1 m one way, 6 mm² (8 AWG) for 3 m, 10 mm² (6 AWG) for 5 m and 25 mm² (4 AWG) for 10 m. For lights, which can take 10%, 4 mm² (12 AWG) is enough at 5 m.
What size cable for 12V 100A?
With a 125 A fuse: 25 mm² (4 AWG) for 1 m one way, 35 mm² (2 AWG) for 3 m, 50 mm² (1/0 AWG) for 5 m and 120 mm² (4/0 AWG) for 10 m. At 1 m the size comes from the fuse the cable has to carry, not from the voltage drop.
Is the length in a wire size chart one way or round trip?
In this chart and in the cable size calculator it’s one way, from the battery to the device; the return on the negative is already counted. Other charts work differently, so check which length they mean before you compare.
How much voltage drop is acceptable on 12V?
3% (0.36 V) for fridges, pumps, electronics and charging cables, 1–2% for the main battery cables, chargers and inverters, and up to 10% for lights.
Does 24V need thinner cable than 12V?
Yes, for the same current: 20 A over 3 m needs 4 mm² (12 AWG) at 24 V and 6 mm² (8 AWG) at 12 V. On short runs the fuse sets the size, and the fuse is the same at both voltages.