JK BMS settings for LiFePO4: every field, its value and the Victron setting that goes with it
For a LiFePO4 pack, load JK’s LiFePO4 preset, set Cell Count and Battery Capacity, then adjust: Cell OVP 3.60 V, Cell OVPR 3.40 V, Cell UVP 2.8 V, Cell UVPR 3.0 V, Start Balance Vol. 3.40 V, Balance Trig. Volt. 0.01 V, and Charge UTP at 0–5 °C instead of the preset’s −20 °C. Your Victron chargers then work below those limits.
These are typical per-cell values that DIY builders and battery makers agree on; your cells’ datasheet wins wherever it says otherwise. Below: the setup order with JK’s default passwords, the full table with each JK field name, why it matters and the matching Victron setting, the rule behind “sending failure”, and how balancing works.
First setup, in this order
- 1
Open JK’s app near the battery and connect. JK’s manual gives 1234 as the default Bluetooth password; change it or remove it there.
- 2
On the settings page tap Authorize Settings and enter the settings password, 123456 by default. It is separate from the Bluetooth password.
- 3
Tap the LiFePO4 button. It loads JK’s one-click LiFePO4 values for every field at once.
- 4
Set Cell Count (4 for 12 V, 8 for 24 V, 16 for 48 V) and Battery Capacity(Ah) before anything else. JK’s manual is clear that the BMS will not work properly with the wrong cell count.
- 5
Change Charge UTP right away: the LiFePO4 preset leaves it at −20 °C, far too low for charging LiFePO4.
- 6
Work through the table below. Send each value with its Set button; the board clicks when it has received it.
- 7
Charge fully once and look at the cell voltages at the top of the charge: the spread between the highest and the lowest cell tells you whether balancing does its job.
Field names change slightly between JK boards and app versions: older apps show Max Charge Curr., newer ones Continued Charge Curr. for the same limit. Newer boards also add Cell RCV, Cell RFV and SOC-100% / SOC-0% voltages, covered further down.
JK BMS settings for LiFePO4: the table
Values are per cell, with the 12 V (4S) equivalent in brackets; multiply by 8 for 24 V and by 16 for 48 V. The last column is where the same limit lives on your Victron side, with Victron’s LiFePO4 preset values.
| JK field | Typical LiFePO4 value | Why | Victron setting that goes with it |
|---|---|---|---|
| Cell OVP(V) | 3.60 V, range 3.55–3.65 V (14.4 V) | Cuts charging when any cell goes too high. A safety net, not the normal end of charge. | Absorption 14.2 V (3.55 V per cell) on MPPT, Orion XS and IP22 stays below it. |
| Cell OVPR(V) | 3.40–3.45 V (13.6–13.8 V) | Charging comes back only after the cells settle; a gap of 0.1 V or more stops the BMS switching on and off at the top. | Float 13.5 V (3.375 V per cell) sits under it. |
| Cell UVP(V) | 2.8 V, range 2.6–2.9 V (11.2 V) | Cuts discharge at the steep end of the curve, where little energy is left and cells take damage. | Your inverter’s low-voltage shutdown should act first, for example at 12.0 V (3.0 V per cell). |
| Cell UVPR(V) | 3.0–3.1 V (12.0–12.4 V) | Discharge returns only after a real recharge, not after the voltage bounces back at rest. | Nothing to set: any charger lifts the cells above it. |
| Power Off Vol.(V) | 2.5 V, the preset (10.0 V) | The BMS shuts itself down so its own draw cannot drain a flat pack. JK: it must be lower than Cell UVP. | Nothing to set; don’t leave the battery flat (see winter storage). |
| Start Balance Vol.(V) | 3.40–3.45 V (13.6–13.8 V) | Above about 3.4 V the voltage tracks charge, so the balancer works where differences are real. | The LiFePO4 preset absorbs at 14.2 V for a fixed 2 h, time the balancer spends above this voltage. |
| Balance Trig. Volt.(V) | 0.01 V; JK suggests 0.005 V for cells above 50 Ah | Smaller differences are close to the measuring tolerance; balancing them only moves energy back and forth. | Nothing to set; check the min and max cell after a full charge. |
| Max Balance Cur.(A) | The board’s maximum (often 1 or 2 A), at most 0.1C per JK’s manual | More balancing current closes a gap faster during the short time at the top. | Nothing to set. |
| Max Charge Curr.(A) / Continued Charge Curr.(A) | Above the sum of your chargers, within the cells’ rating (often 0.5C) | Catches a fault; normal charging should never reach it. | MPPT, Orion XS and shore charger maximum currents added together stay below it. |
| Max Discharge Curr.(A) / Continued Discharge Curr.(A) | Your inverter and loads at full power, within the board and cable rating | Cuts discharge on a fault or an overload that lasts longer than the Discharge OCP Delay. | Inverter or MultiPlus size and its fuse. |
| Charge OTP(℃) | 45–55 °C (preset 60 °C) | Charging hot cells ages them quickly. | Nothing to set in the LiFePO4 preset: the BMS covers it. |
| Charge UTP(℃) / UTPR | 0–5 °C, recovery about 5 °C higher (preset −20 / −10 °C) | Charging LiFePO4 below 0 °C plates lithium on the anode and costs capacity for good. | MPPT low-temperature cut-off, 5 °C by Victron’s default, works only with a battery temperature from a VE.Smart network. |
| Discharge OTP(℃) | 55–60 °C | Protects cells and board when hot. | Nothing to set. |
Typical values, not a recipe. They match the ranges in JK’s manual, battery makers’ JK parameter sheets and the long DIY threads. If your cells’ datasheet gives a different maximum voltage, charge current or lowest charging temperature, use the datasheet.
Why the JK app says “sending failure”
The board refuses a value that breaks the order of the voltages, and the app answers with “sending failure”. From the bottom up, LiFePO4 values must stay in this order, each one clearly above the previous one:
- Power Off Vol. below Cell UVP, below Cell UVPR.
- Cell OVPR below Cell OVP.
- On newer boards: Cell OVPR below SOC-100% Vol., below Cell RCV, and RCV clearly below Cell OVP.
- Equal values count as a break: leave a margin, around 0.1 V between a protection value and its recovery.
When you move a whole range, change the value that makes room first. Raising OVP and OVPR: send OVP first, then OVPR. Lowering UVP and UVPR: send UVP first, then UVPR.
The BMS protects, the charger controls
A JK BMS stops charging by opening its MOSFETs when a limit is hit. That is protection: abrupt, and meant for when something goes wrong. The day-to-day charge belongs to your chargers, the SmartSolar MPPT, the Orion XS from the alternator and the IP22 or MultiPlus on shore power. They should finish the charge on their own, below the BMS limits, so the BMS never has to step in.
With Victron’s LiFePO4 preset the margins line up: absorption 14.2 V is 3.55 V per cell, under a Cell OVP of 3.60–3.65 V; float 13.5 V sits under Cell OVPR. If you set OVP as low as 3.55 V, the absorption voltage reaches it, and a single cell slightly ahead trips the BMS at every full charge. Either keep OVP at 3.60 V or more, or lower the chargers’ absorption voltage. Every Victron device and its values: Victron LiFePO4 settings; the solar charger in detail: MPPT LiFePO4 settings.
Newer JK boards add Cell RCV and Cell RFV (the charge and float voltage per cell) and SOC-100% / SOC-0% Vol. RCV and RFV steer charging only when the BMS is linked by cable to an inverter that follows its requests; with Victron chargers over Bluetooth you set the voltages on the chargers. Keep RCV near your absorption voltage per cell (3.45–3.55 V), RFV near float (3.35–3.40 V), and SOC-100% between OVPR and RCV, so the order above holds.
Balancing: when it runs and why at the top
JK boards balance actively: they move energy from the highest cell to the lowest instead of burning it off. Balancing runs only while both conditions hold: a cell is above Start Balance Vol. and the gap between the highest and the lowest cell is larger than Balance Trig. Volt. It stops as soon as one of them is no longer true.
The start voltage matters most. Between roughly 3.2 and 3.35 V a LiFePO4 cell’s voltage barely moves with charge (the flat part of the LiFePO4 voltage chart), so differences there say little and balancing on them can push cells further apart. Above 3.4 V the curve climbs and a higher cell really holds more charge. That is why the balancer is set to work at the top of the charge, and why the chargers need enough time there: Victron’s LiFePO4 preset uses a fixed 2-hour absorption and a tail current of 0 A for exactly this reason.
With a new self-built pack, the cells are usually top-balanced in parallel before you assemble them; after that the BMS keeps them close at the top of each full charge. After a few full charges the spread at the top should shrink to a few millivolts; if it keeps growing, check the balance wires (the app shows their resistance) before changing values.
Check balancing from your iPhone with Deeck
Deeck reads JK (Jikong) boards over Bluetooth with Deeck Plus: state of charge, voltage, current, cell voltages and temperatures, next to your Victron devices, on the Apple Watch, and through Deeck Bridge in the Cerbo GX, VRM and CarPlay. Seeing the minimum and maximum cell next to the MPPT during absorption is a quick way to check that balancing works after you have set it.
Protection limits, balancing settings and the password stay in JK’s app: Deeck reads, it doesn’t change settings. If Deeck says the battery asks for a password, remove the Bluetooth password in JK’s app. Deeck recognises JK by its protocol; I haven’t tested it on a real system yet: if anything looks off, tell me and I’ll fix it. More on what Deeck shows: JK BMS app on iPhone.
JK and Jikong are trademarks of their owner and are used here only to describe compatibility. Deeck is not affiliated with JK.
Questions people ask
What should I set on a JK BMS for LiFePO4?
Load the LiFePO4 preset, set Cell Count and Battery Capacity, then typically Cell OVP 3.60 V, OVPR 3.40 V, UVP 2.8 V, UVPR 3.0 V, Start Balance Vol. 3.40 V, Balance Trig. Volt. 0.01 V and Charge UTP 0–5 °C. Your cells’ datasheet wins where it differs.
What is the default JK BMS password?
According to JK’s manual, 1234 for the Bluetooth connection and 123456 for changing settings (Authorize Settings). The two are independent; you can change both in JK’s app.
Why does the JK app show “sending failure”?
The new value breaks the order of the voltages, for example OVPR equal to or above OVP, or Power Off Vol. above UVP. Keep each value clearly above the one below it, and when you move a range, send the value that makes room first.
Can Deeck change my JK BMS settings?
No. Deeck reads JK boards with Deeck Plus (charge, voltage, current, cells and temperatures) next to your Victron devices; protection limits, balancing settings and the password stay in JK’s app.